Theory Of Operation High pressure liquid flows into receiver-dryer where moisture and contaminants (acid, solids, etc.) are removed. Receiver-dryer contains a color moisture indicator. (Blue) indicates no moisture is present. (Pink) indicates moisture is present. Should moisture be combined with refrigerant, hydrofluoric and hydrochloric acids are formed. These acids are very corrosive to metal surfaces and leakage will eventually develop. Receiver-dryer also stores refrigerant allowing a longer period of time before additional refrigerant is needed. Refrigerant hoses will allow a small amount of refrigerant to migrate through their walls.
Actual cooling and drying of cab air takes place at evaporator. Heat absorbed by evaporator and transferred to refrigerant causes refrigerant to vaporize into low pressure gas. Low pressure gas is drawn from evaporator by compressor and cycle is repeated. A freeze control switch senses temperature of evaporator coil through a capillary tube. This prevents the evaporator from becoming cold enough to freeze moisture that condenses on evaporator coil. Condensed moisture is drained away through drain tubes connected to drain pan under evaporator. Refrigerant flows from receiver-dryer through expansion valve to evaporator.
Expansion valve senses refrigerant temperature and pressure to modulate refrigerant flow. Expansion valve changes refrigerant to low pressure liquid entering evaporator. System pressure is monitored by the high and low pressure switch, located at the receiver-dryer. If pressure becomes too high or too low the switch opens and stops compressor, interrupting the cycle. MD46667,0000005 –19–09FEB06–2/2 9031 05 2 TM2361 (24JUN08) 9031-05-2 450DLC Excavator Operation and Tests 062608 PN=952