© 1283 Temperature Switch (OIl, Water, Air) Testing / Reconditioning Job Card No.: 11.01.01 Page 1 of 3 Engine: S/BVM 628 Filing No.: 0178-48-10 1189 Testing Tools: - Standard tools Check the switch for correct setting and proper - Ohmmeter functioning. - Thermometer The switch comprises sensor (1) with pocket (2) - test - Heat conducting compound site - and a setting unit (4) - cable terminal box -. Be sure lead (7) between setting unit (4) and sensor (1) will not chafe. Job Clean sensor (1) externally and check that it is firmly seated. Setting: Refer to the section 3.3 ”Technical Specifications” for the set point values of the temperature switch trip points.
The trip point (see 3.3) is set on dial (3) of unit (4) with an accuracy of 2.5 % over the entire tempe- rature range. a) Testing the Sensor (1) Remove sensor (1) from pocket (2) and dip in hot water. Use and ohmmeter to meet the electrical resistance. By means of curves on sheet (3), compare actual and specified values, or test as under c). b) Testing the Setting Unit (4) Remove unit (4) from terminal box and connect to terminals (3) and (4) of sensor (1) in water by means of two 1.5 mm2 leads. Apply auxiliary voltage of 24 volts to terminals (1) and (2). Con- nect ohmmeter to terminals (5) and (6). Adjust dial (3) to determine trip point and compare with wa- ter temperature.
If test result is satisfactory, seal unit with lead, or test as under c). c) Testing Sensor (1) plus Setting Unit (4) as a Whole (alternatively) Use test instrument TP 100/12 supplied by Noris Techometerwerk GmbH & Co., Muggenhofer Str. 95, 8500 Nürnberg, Germany. © 51 354 0 © 51 354 0 © 51 354 0