Heating and Air Conditioning 5. Do air conditioner checks and tests in Operation and Test Manual, Groups 9005-10 and 9031-25. CED,TX14826,12325 –19–04MAY00–2/2 Leak Testing 18 1830 20 JT02081 Electronic Leak Detector SERVICE EQUIPMENT AND TOOLS 1. Inspect all lines, fittings, and components for oily or dusty spots. When refrigerant leaks from the system, a small amount of oil is carried out with it. 2. A soap and water solution can be sprayed on the components in the system to form bubbles at the source of the leak. 3. If a leak detector is used, move the leak detector probe under the hoses and around the connections at a rate of 25 mm (1 in.) per second. 4.
Some refrigerant manufacturers add dye to refrigerant to aid in leak detection. CED,OUO1066,309 –19–30MAR00–1/1 TM1859 (14JUL04) 18-1830-20 700H Crawler Dozer 071404 PN=464 SPECIFICATIONS Leak Detector Probe Rate 25 mm (1 in.) per Second