Victron Energy · MultiPlus-II · 4 pp.
Victron Energy MultiPlus-II Inverter/Charger Certificate of Conformity PDF
Сертификат соответствия, подтверждающий соответствие продукта требованиям стандарта PTPiREE Rev1.2 и регулирования NC Code RfG для подключения генераторов к электрическим сетям.
Related manuals
Document text
Certificate of Conformity By the product certificate number No. 2622/0478-O- CER/E1 Issued to: License holder and producer: Victron Energy B. V. De Paal 35, 1351 JG Almere – Netherlands Trademark: Contract number: 802190 It is certified that the product: Type of product: Inverter/Charger with UPS functionality Product Family: MultiPlus-II Models: 48/8000/110-100 230V // 48/10000/140-100 230V // 48/15000/200-100 230V 48/3000/35-32 230V // 24/3000/70-32 230V // 24/5000/120-50 230V // 48/5000/70-50 230V 48/3000/35-32 GX 230V // 24/3000/70-32 GX 230V // 48/5000/70-50 GX 230V Technical Data:
Rated AC Power See page 2 Rated AC Voltage 230 VAC Rated AC Frequency 50 Hz Firmware version See page 2 Number of phases Single Phase (L/N/PE) Isolation transformer Yes Is in compliance with product requirements of the standard: - PTPiREE Rev1.2:2021, “ Conditions and procedures for using certificates in the process of connecting power generation modules to power networks” ( 1 ) Is in compliance with the requirements of regulation:
- NC Code RfG, Regulation (UE) 2016/631 COMMISSION REGULATION (EU) 2016/631 of 14 April 2016 establishing a network code on requirements for grid connection of generators - Generally applicable requirements resulting from Commission Regulation (EU) 2016/631 of 14 April 2016 laying down the network code concerning the requirements for connection of generating units to the grid (NC RfG)”- approved by the Decision of the President of the Energy Regulatory Office DRE.WOSE.7128.550.2.2018.ZJ of 2 January 2019 ( 1 ) Certified requirements only related to PTPiREE Rev1.2 clauses 7 and 9. The Functions denoted “Not Applicable” in table 2 of clause 7, have not been included.
See page 3 for more details regarding the standardґs requirements that are evaluated and in compliance under the scope of this certificate . This certificate is based upon the test results of the Test Report 2622/0478-O & 2622/0478-P issued by SGS. It is certified that Power Generating Unit (PGE) above indicated are in compliance with requirements detailed in the above referenced standard for grid connections of type A. Aforementioned equipment is certified according to SGS internal procedure PE.T-ECPE-70 according to requirements established on standard UNE-EN ISO/IEC 17065. This certificate cancels and supersedes certificate No.
2622/0478-O-CER This certificate is first issued on 18 th April 2024. This certificate is valid until the 18 th April 2029. Madrid, 12 th August 2024. Daniel Arranz Muciz Certification Manager SGS Tecnos, S.A.U. C/ Trespaderne, 29 - 28042 Madrid This certificate is issued by SGS under its General Conditions for Product Certification at www.sgs.com/terms_and_conditions. The status and validity of the certificate can be checked scanning the QR code above included or through the following web link . This document cannot be reproduced partially No. 2622/0478-O-CER/E1 Page 1 de 4
Full list of product references and nominal characteristics: SGS Tecnos, S.A.U. C/ Trespaderne, 29 - 28042 Madrid This certificate is issued by SGS under its General Conditions for Product Certification at www.sgs.com/terms_and_conditions. The status and validity of the certificate can be checked scanning the QR code above included or through the following web link . This document cannot be reproduced partially No. 2622/0478-O-CER/E1 Page 2 de 4 Family MultiPlus-II Model 48/8000/110-100 48/10000/140-100 48/15000/200-100 24/5000/120-50 230V 230V 230V 230V AC Input Input voltage range 187 – 265 VAC Input frequency 45 - 65 Hz Max.
battery charge current 110 A 140 A 200 A 120 AC Output Rated active power 6400 W 8000 W 12000 W 4000W Max. active power 8000 VA 10000 VA 15000 kVA 5000VA Rated AC Voltage 230 VAC L/N/PE Firmware version 2621510 2627510 2619510 2615510 Family MultiPlus-II Model 48/3000/35-32 230V 24/3000/70-32 230V 48/5000/70-50 230V AC Input Input voltage range 187 – 265 VAC Input frequency 45 - 65 Hz Max. battery charge current 35 A 70 A 70 A AC Output Rated active power 2400 W 2400 W 4000 W Max.
active power 3000 VA 3000 VA 5000 VA Rated AC Voltage 230 VAC L/N/PE Firmware version 2629510 2611510 2623510 Family MultiPlus-II Model 48/3000/35-32 GX 230V 24/3000/70-32 GX 48/5000/70-50 GX 230V 230V AC Input Input voltage range 187 – 265 VAC Input frequency 45 - 65 Hz Max. battery charge current 35 A 70 A 70 A AC Output Rated active power 2400 W 2400 W 4000 W Max. active power 3000 VA 3000 VA 5000 VA Rated AC Voltage 230 VAC L/N/PE Firmware version 2629510 2611510 2623510
SGS Tecnos, S.A.U. C/ Trespaderne, 29 - 28042 Madrid This certificate is issued by SGS under its General Conditions for Product Certification at www.sgs.com/terms_and_conditions. The status and validity of the certificate can be checked scanning the QR code above included or through the following web link . This document cannot be reproduced partially No. 2622/0478-O-CER/E1 Page 3 de 4 Requirements description acc. PTPiREE Rev1.2 Generally applicable requirements NC RfG Type Compliant Name of Ev.(2) Issuing Entity Power-frequency regulation mode limited to overfrequency (LFSM-O) Article13, 2, a) Article13, 2, b) Article 13, 2, f) ≥A YES (TRF No.
2622/0478-O & 2622/0478-P) SGS P Power-frequency regulation mode limited to underfrequency (LFSM-U) Article 15, 2, c), i) ≥C Not Applicable -- N/A Fast fault current injection at the connection point in case of symmetrical (3-phase) faults Article 20, 2, b) Article 20, 2, c) ≥B Not Applicable -- N/A FRT Article 20, 2, b) Article 20, 2, c) ≥B Not Applicable -- N/A Recovery of active power after a fault Article 20, 3, a) ≥B Not Applicable -- N/A Cessation of active power Article 13, 6 A&B YES (TRF No. 2622/0478-O & 2622/0478-P) SGS P Remote Control PGM Type B Article 14, 2 B Not Applicable -- N/A Frequency operation field Article 13, 1, a) ≥A YES (TRF No.
2622/0478-O & 2622/0478-P) SGS P ROCOF Article 13, 1, b) ≥A YES (TRF No. 2622/0478-O & 2622/0478-P) SGS P (2) Note: - P: Test of compliance - N/A: Not applicable
ANNEX I: POLAND PARAMETER TABLE SGS Tecnos, S.A.U. C/ Trespaderne, 29 - 28042 Madrid This certificate is issued by SGS under its General Conditions for Product Certification at www.sgs.com/terms_and_conditions. The status and validity of the certificate can be checked scanning the QR code above included or through the following web link . This document cannot be reproduced partially No.
2622/0478-O-CER/E1 Page 4 de 4 Clause(s) / subclause(s) of Remarks / Configurable EN 50549-1:2019 or Parameter Additional information Value / Range EN 50549-2:2019 4.4.2 Operating frequency range 47.5 – 48.5 Hz Duration 30 mins 48.5 – 49.0 Hz Duration Unlimited 49.0 – 51.0 Hz Duration Unlimited 51.0 – 51.5 Hz Duration 30 mins 4.5.2 Rate of change of frequency (ROCOF) immunity ROCOF withstand capability 2 Hz/s 4.6.1 Power response to overfrequency Threshold frequency f1 50.2 Hz – 50.5 Hz Droop 2 % – 12 % Power reference Pmax Intentional delay 0 Deactivation threshold fstop f1 Deactivation time tstop N/A 4.11.1 Ceasing active power Activation option The communication port is classified as input port “AUX 1” Digital input.