Chapter 12 Description of Parameter Settings CFP2000 LOCAL / REMOTE Selection Default: 0 Settings 0: Standard HOA function 1: Switch Local / Remote, the drive stops 2: Switch Local / Remote, the drive runs as the REMOTE setting for frequency and operation status 3: Switch Local / Remote, the drive runs as the LOCAL setting for frequency and operation status 4: Switch Local / Remote, the drive runs as LOCAL setting when switched to Local, and runs as REMOTE setting when switch to Remote for frequency and operation status. The default for Pr.00-29 is 0 (standard Hand-Off-Auto function). Set the AUTO frequency and operation source with Pr.00-20 and Pr.00-21.
Set the HAND frequency and operation source with Pr.00-30 and Pr.00-31. Select or switch AUTO / HAND mode by using the digital keypad KPC-CC01 or setting the multi-function input terminal MIx= 41, 42. When you set the external terminal (MI) to 41 and 42 (AUTO / HAND mode), Pr.00-29=1, 2, 3, 4 are disabled. The external terminal has the highest command priority, and Pr.00-29 functions in standard HOA mode. When you do not set Pr.00-29 to 0, the Local / Remote function is enabled, and the top right corner of digital keypad KPC-CC01 (firmware version 1.021 and above) displays “LOC” or “REM”. Set the REMOTE frequency and operation source with Pr.00-20 and Pr.00-21.
Set the LOCAL frequency and operation source with Pr.00-30 and Pr.00-31. Select or switch Local / Remote mode with the digital keypad KPC-CC01 or set the multi-function input terminal MIx=56. The AUTO key of the digital keypad is for the REMOTE function, and HAND key is for the LOCAL function. When you set the external terminal (MI) to 56 for LOC / REM mode selection, if you set Pr.00-29 to 0, then the external terminal function is disabled. When you set the external terminal (MI) to 56 for LOC / REM mode selection, if Pr.00-29 is not set to 0, then AUTO / HAND key is disabled, and the external terminal has the highest command priority.
Following table is the corresponded setting value for the PLC address: 12.1-00-12 PLC address / Mode HOA mode LOC / REM mode HOA mode HAND-ON AUTO-ON LOC-ON REM-ON OFF M1090 = 0 0 0 0 1 M1091 = 1 0 0 0 0 M1092 = 0 1 0 0 0 M1100 = 0 0 1 0 0 M1101 = 0 0 0 1 0