Chapter 12 Description of Parameter Settings  CFP2000 LOCAL / REMOTE Selection Default: 0 Settings 0: Standard HOA function 1: Switch Local / Remote, the drive stops 2: Switch Local / Remote, the drive runs as the REMOTE setting for frequency and operation status 3: Switch Local / Remote, the drive runs as the LOCAL setting for frequency and operation status 4: Switch Local / Remote, the drive runs as LOCAL setting when switched to Local, and runs as REMOTE setting when switch to Remote for frequency and operation status.  The default for Pr.00-29 is 0 (standard Hand-Off-Auto function). Set the AUTO frequency and operation source with Pr.00-20 and Pr.00-21.

Set the HAND frequency and operation source with Pr.00-30 and Pr.00-31. Select or switch AUTO / HAND mode by using the digital keypad KPC-CC01 or setting the multi-function input terminal MIx= 41, 42.  When you set the external terminal (MI) to 41 and 42 (AUTO / HAND mode), Pr.00-29=1, 2, 3, 4 are disabled. The external terminal has the highest command priority, and Pr.00-29 functions in standard HOA mode.  When you do not set Pr.00-29 to 0, the Local / Remote function is enabled, and the top right corner of digital keypad KPC-CC01 (firmware version 1.021 and above) displays “LOC” or “REM”. Set the REMOTE frequency and operation source with Pr.00-20 and Pr.00-21.

Set the LOCAL frequency and operation source with Pr.00-30 and Pr.00-31. Select or switch Local / Remote mode with the digital keypad KPC-CC01 or set the multi-function input terminal MIx=56. The AUTO key of the digital keypad is for the REMOTE function, and HAND key is for the LOCAL function.  When you set the external terminal (MI) to 56 for LOC / REM mode selection, if you set Pr.00-29 to 0, then the external terminal function is disabled.  When you set the external terminal (MI) to 56 for LOC / REM mode selection, if Pr.00-29 is not set to 0, then AUTO / HAND key is disabled, and the external terminal has the highest command priority.

 Following table is the corresponded setting value for the PLC address: 12.1-00-12 PLC address / Mode HOA mode LOC / REM mode HOA mode HAND-ON AUTO-ON LOC-ON REM-ON OFF M1090 = 0 0 0 0 1 M1091 = 1 0 0 0 0 M1092 = 0 1 0 0 0 M1100 = 0 0 1 0 0 M1101 = 0 0 0 1 0