Chapter 12 Description of Parameter Settings  CFP2000 Number of poles for Induction Motor 1 Default: 4 Settings 2–64  Sets the number poles for the motor (must be an even number).  Set up Pr.01-01 and Pr.05-03 before setting up Pr.05-04 to make sure motor operates normally. Pr.01-01 and Pr.05-03 determine the maximum set up number poles for the IM. For example: Pr.01-01=20 Hz and Pr.05-03=39 rpm, according to the equation 120 x 20 Hz / 39 rpm=61.5 and take even number, the number of poles is 60. Therefore, Pr.05-04 can be set to the maximum of 60 poles. No-load Current for Induction Motor 1 (A) Default:

Depending on the model power Settings 0.0–Pr.05-01 default  The default is 10–40% of motor rated current.  For model with 110 kW and above, default setting is 20% of motor rated current. Stator Resistance (Rs) for Induction Motor 1 Default: Depending on the model power Settings 0.000–65.535 Ω Rotor Resistance (Rr) for Induction Motor 1 Default: 0.000 Settings 0.000–65.535 Ω Magnetizing Inductance (Lm) for Induction Motor 1 Stator inductance (Lx) for Induction Motor 1 Default: 0.0 Settings 0.0–6553.5 mH Full-load Current for Induction Motor 2 (A) Default:

Depending on the model power Settings Depending on the model power  Set this value according to the rated current of the motor as indicated on the motor nameplate. The default is 90% of the drive’s rated current. Example: The rated current for a 7.5 HP (5.5 kW) motor is 25 A. The default is 22.5 A. The setting range is between 2.5–30 A. (25*10%=2.5 A and 25*120%=30 A)  Rated Power for Induction Motor 2 (kW) Default: Depending on the model power Settings 0.00–655.35 kW  Set the rated power for motor 2. The default is the drive’s power value. 12.1-05-2