Chapter 12 Description of Parameter Settings  CFP2000 brake is invalid when Pr.07-03 is set to 0.0. Related parameters: Pr.00-22 Stop Method, Pr.07-04 DC Brake Frequency at STOP.  DC Brake Frequency at STOP Default: 0.00 Settings 0.00–599.00 Hz  This parameter determines the start frequency of the DC brake before the drive ramps to stop. When this setting is less than Pr.01-09 (Start-up Frequency), the start frequency of the DC brake starts from the minimum frequency.  Use the DC brake before running the motor when the load is movable at stop, such as with fans and pumps.

The motor is in free operating status and in unknown rotation direction before the  Use DC brake at STOP when you need to brake the motor quickly or to control the positioning, drive start up. Execute the DC brake before you start the motor. such as with cranes or cutting machines.  Voltage Increasing Gain Default: 100 Settings 1–200%  When using speed tracking, adjust Pr.07-05 to slow down the increasing voltage gain if there are errors such as oL or oc; however, the speed tracking time will be longer.  Restart after Momentary Power Loss Default: 0 Settings 0: Stop operation 1: Speed tracking by speed before the power loss 2:

Speed tracking by minimum output frequency  Determines the operation mode when the drive restarts from a momentary power loss.  The power system connected to the drive may power off momentarily due to many reasons. This function allows the drive to keep outputting after the power is repowered and does not cause the drive to stop.  Setting 1: Frequency tracking begins before momentary power loss and accelerates to the master Frequency command after the drive output frequency and motor rotator speed are synchronous. Use this setting when there is a lot of inertia with little resistance on the motor load.

For example, in equipment with a large inertia flywheel, there is NO need to wait until the flywheel stops completely after a restart to execute the operation command; therefore, it saves time. 12.1-07-2