Chapter 6 Control Terminals CFP2000 6-8 Terminals Terminal Function Factory Setting (NPN mode) MI1 | MI8 Multi-function input 1–8 Refer to parameters 02-01–02-08 to program the multi-function inputs MI1–MI8. Source Mode ON: the activation voltage ≥ 11 V DC OFF: cut-off current voltage ≤ 5 V DC Sink Mode ON: the activation voltage ≤ 13 V DC OFF: cut-off current voltage ≥ 19 V DC The internal resistance is 3.6 kΩ. DCM Digital frequency signal common Digital frequency signal common RA1 Multi-function relay output 1 (N.O.) a Resistive Load: 3A (N.O.) / 3A (N.C.) 250 V AC 5A (N.O.) / 3A (N.C.) 30 V DC Inductive Load (COS 0.4):
1.2A (N.O) / 1.2A (N.C.) 250 V AC Various kinds of monitor signals output, e.g. operation, frequency reached, overload indication, etc. RB1 Multi-function relay output 1 (N.C.) b RC1 Multi-function relay common RA2 Multi-function relay output 2 (N.O.) a Resistive Load: 3A (N.O.) / 250 V AC 5A (N.O.) / 30 V DC Inductive Load (COS 0.4): 1.2A (N.O.) / 250 V AC Various kinds of monitor signals output, e.g. operation, frequency reached, overload indication, etc. RC2 Multi-function relay common RA3 Multi-function relay output 3 (N.O.) a RC3 Multi-function relay common +10V Potentiometer power supply Analog frequency setting: +10 V 20 mA DC AVI1 Analog voltage input Figure 6-19 Impedance:
20 kΩ Range: 0–20 mA / 4–20 mA / 0–10 V = 0–Max. Output Frequency (Pr.01-00) AVI1 switch, default is 0–10 V ACI Analog current input Figure 6-20 Impedance: 250 Ω Range: 0–20 mA / 4–20 mA / 0–10 V = 0–Max. Output Frequency (Pr.01-00) ACI Switch, default is 4–20 mA