3RV Motor Starter Protectors/Circuit Breakers up to 100 A General data Schematics Internal circuit diagrams Motor starter protector/ circuit breaker Motor starter protector with overload relay function Motor starter protector Voltage transformer circuit breaker 3RV10 .., 3RV14 .., 3RV16 11-0BD10, 3RV17 .., 3RV18 .. 3RV11 .. 3RV13 ..
3RV16 11-1.G14 Distance protection and starting Starting 5 11 NSB0_01105b 14 12 from voltage transformer unit Switching examples 3RV11 motor starter protector with overload relay function 3RV16 11-1.G14 voltage transformer circuit breaker L1 F1 OFF Button S1 ON Button S2 Self-holding contact K1 Fuse (gL/gG) 6 A F1, F2 Undervoltage trip unit 3RV11 Q1 12 14 + S1 S2 K1 11 Q1 K1 NSB0_00025c ! " # % & ' ( ) * + ' , " - . ' ( % N(L2) F2 NSB0_01106b Note: When using the NO contact to connect the voltage transformer circuit breaker, the binary input of the distance protection device (Siemens 7 SA xxx) should be set to "active without voltage".
This connection type is used for additional monitoring of correct wiring. More information Conversion of voltage transformer circuit breakers 3VU13 to 3RV1 The 3VU13 voltage transformer motor starter protectors previ- ously available have been discontinued. The 3RV1 voltage transformer motor starter protectors are offered as replacement types. 27 Siemens · 2009 1 3 v v v 2 4 Previous type Replacement type 3VU13 11-6HR00 3RV16 11-1CG14 3VU13 21-6HR00 3RV16 11-1CG14 + 3RV19 01-1A 3VU13 11-6JR00 3RV16 11-1DG14