Siemens — General data

Solid-State Switching Devices for Resistive Loads 3RF29 Function Modules General data 1) Versions are independent of the main circuit. 45 Siemens · 2009 Type 3RF29 ..-.E..8 3RF29 ..-.F..8 3RF29 ..-.G..3 3RF29 ..-.G..6 Main circuit Rated operational voltage Ue V • Operating range V • Rated frequency Hz -- 1) 110 ... 230 400 ... 600 -- 93.5 ... 253 340 ... 660 -- 50/60 Rated insulation voltage Ui V -- 600 Voltage measuring • Measuring range V -- 93.5 ... 253 340 ...

660 Mains voltage, fluctuation % compensation -- 20 Type 3RF29 ..-.H..3 3RF29 ..-.K..3 3RF29 ..-.H..6 3RF29 ..-.K..6 3RF29 ..-.J..3 3RF29 ..-.J..6 Main circuit Rated operational voltage Ue V • Operating range V • Rated frequency Hz 110 ... 230 400 ... 600 110 ... 230 400 ... 600 93.5 ... 253 340 ... 660 93.5 ... 253 340 ... 660 50/60 Rated insulation voltage Ui V 600 Voltage measuring • Measuring range V 93.5 ... 253 340 ... 660 93.5 ... 253 340 ... 660 Mains voltage, fluctuation % compensation 20 Type 3RF29 ..-...0. 3RF29 ..-...1. 3RF29 ..-...3.

Control circuit Method of operation DC operation AC/DC operation AC operation Rated control supply voltage Us V Rated control current mA 24 24 110 15 15 15 Rated frequency Hz of the control supply voltage -- 50/60 50/60 Actuating voltage, max. V Rated control current mA At maximum voltage 30 30 121 15 15 15 Response voltage V • For operating current mA 15 15 90 2 2 2 Drop-out voltage V 5 5 15 Type 3RF29 06-0FA08 3RF29 20-0FA08 3RF29 20-0GA.. 3RF29 50-0GA.. 3RF29 90-0GA.. Current measurement Rated operational current Ie A 6 20 20 50 90 Current measurement • Teach range A • Measuring range A • Minimum partial load current A 0.25 ... 6 0.65 ... 20 0.56 ... 20 1.62 ... 50 2.93 ... 90 0 ...

6.6 0 ... 22 0 … 22 0 … 55 0 … 99 0.25 0.65 0.65 1.6 2.9 Number of partial loads 1 ... 6 1 ... 6 1 ... 12 Type 3RF29 20-0HA.. 3RF29 50-0HA.. 3RF29 90-0HA.. 3RF29 16-0JA.. 3RF29 32-0JA.. Current measurement Rated operational current Ie A 20 50 90 16 32 Current measurement • Teach range A • Measuring range A • Minimum partial load current A 4 ... 20 10 ... 50 18 ... 90 0.42 ... 16 0.8 ... 32 0 ... 22 0 ... 55 4 ... 99 0 ... 16 0 ... 32 -- 0.42 0.8 Number of partial loads -- 1 ... 6 Type 3RF29 04-0KA.. 3RF29 20-0KA.. 3RF29 50-0KA.. 3RF29 90-0KA..

Current measurement Rated operational current Ie A 4 20 50 90 Current measurement • Teach range A • Measuring range A • Minimum partial load current A 0.15 ... 4 0.65 ... 20 1.6 ... 50 2.9 ... 90 0 ... 4 0 ... 22 0 ... 55 0 ... 99 -- 0.65 1.6 2.9 Number of partial loads 1 ... 6