Chapter 5 Communication | CME-PD01 „ T1: transmission time between Master and CME-PD01 „ T2: waiting time for CME-PD01 buffer „ T3: transmission time between CME-PD01 and VFD-E Timer CME-PD01 VFD series Drives Master Data Buffer T1 T3 T2 T1 depends on the actual transmission speed and the type of master in use. T2 depends on the internal timer of CME-PD01. Data is transmitted to VFD-E series per 70ms triggered by a timer. User cannot change the time-out interval. T3 depends on the Modbus communication between CME-PD01 and VFD-E series. So the response (refresh) time is, Max. response (refresh) time = T1 + T2 (70ms) + T3 In fact, the actual response (refresh) time is less than the Max.
response (refresh) time. When the data is send to CME-PD01, CME-PD01 will save the data to data buffer. If the timer is in time-out, the data will be transmitted to VFD-E immediately. 5-10 Revision October 2006, 2006PDD23000013