Delta Electronics CME — 6.2 Parameters Settings

Chapter 6 Parameters Setting in GSD file | CME-PD01 If the address in Data Output 1 ~ Data Output 4 is continuous, then set d_state to 1, CME-PD01 will get starting address from Data Output 1. The next data will be got from the address next to the starting address, and the reading length is determined by dout_len. If the MODBUS address for reading is discontinuous, please set d_state to 0, CME-PD01 will also get starting address from Data Output 1, but the difference is other data will be got from the address saved in Data Output 2, Data Output 3 and Data Output 4 in order.

Example, if Data Output 1 = 0x2100; Data Output 2 = 0x2101; Data Output 3 = 0x2102; 6-6 Revision October 2006, 2006PDD23000013 Item Name Type Description Default UINT This is a MODBUS address. CME-PD01 will 0x2104 8 Data Output 4 monitor this address, and copy the return data to the 4th word of cyclic input data PZD if selecting module "4 PKW, 4 PZD". 9 d state _ UINT This is a flag. If address in Data Output 1 ~ Data Output 4 is continuous, set it to 1 or set it to 0. 0x0001 UINT This is a length, and unit is word. It specifies the 0x0002 length of CME-PD01 to process data in PZD.

If 10 din len _ user selects module "4 PKW, 4 PZD", but din len is 3, CME-PD01 will process 3 word _ and ignore the 4th word. 11 dout len _ UINT This is a length, and unit is word. It specifies the length of CME-PD01 to monitor data from the AC Drive. If user selects module "4 PKW, 4 PZD", but dout len is 3, CME-PD01 will monitor _ 3 word and ignore the 4th word. 0x0002 UINT It is used to decide the method when 0x0001 communication with Profibus network is lost. The settings can be: 12 LossDPComTreat 00 – Ignore event and continue; 01 – Stop according to Pr “Stop Method” in VFD-E.

13 LossSPComTreat UINT It is used to decide the method when the SP communication (SCANport communication) is lost. The settings can be: 00 – Stop data exchange and have fault; 01 – Continue data exchange and alarm; 02 – Ignore and continue data exchange. 0x0000