Delta Electronics CME — 7.2 Diagnostic Data

Chapter 7 Troubleshooting | CME-PD01 „ SP LED If both SP LED and NET LED are in steady orange, it indicates that CME-PD01 is in “test mode”. Please do not set the communication address of CME-PD01 to 0XFF at this time. Be sure to set it to other value and re-power on the CME-PD01. 7.2 Diagnostic Data CME-PD01 provides 16 bytes diagnostic data when the abnormal communication occurs or parameter “LossSPComTreat” is set to “Continue data exchange and report alarm”. It includes 6 bytes standard diagnostic data and 10 bytes device related diagnostic data. The following table shows the meanings of the 16 bytes: Byte 7 indicates the length of device related diagnostic data, including itself.

So if byte 7 is 10 (0Ahex), it indicates it has 10 bytes (including byte 7) for the device related diagnostic data. shown as follows: Byte 8 indicates the SP communication status when the error occurs, and the valid value should be 7-2 Revision October 2006, 2006PDD23000013 State Indication Corrective Actions LED is off No power 1. Verify that the power supply of CME-PD01 2. Check whether the power supply is connected and that power is applied to the CME-PD01 through the connector Flashing Red Check if the communication setting in VFD-E is CRC check error LED (9600, , RTU) Red LED Connection failure, or no connection 1.

Check whether the connection between the VFD-E and RS485 of CME-PD01 is correct 2. Re-connect and ensure that the wire specification is correct 1. Check the AC Drive type and version. Flashing AC Drive returns error 2. Check the PLC program, and ensure the Green LED code communication address in CME-PD01 is correct. Green LED Operating normally NOTE Bytes 1-6 Byte 7 Byte 8 Byte 9 Bytes 10-16 Standard diagnostic data Length in bytes SP communication status Error code Reserved