Environment for Operation, Storage and Transportation Specification for Operation Temperature and Protection Level * 1 When the carrier wave for light duty is 2 kHz, the maximum operation temperature can reach up to 50 ° C 8 DO NOT expose the AC motor drive to harsh environments, such as dust, direct sunlight, corrosive / flammable gasses, humidity, liquid or vibrations. The salts in the air must be less than 0.01 mg / cm2 per year. Environment Installation Location IEC60364-1 / IEC60664-1 Pollution degree 2, indoor use only Surrounding Temperature Storage / Transportation (ºC ) -25 ~ 70 Non-condensation, non-frozen Rated Humidity Operation Max. 95% Storage / Transportation Max.

95% No condense water Air Pressure Operation / Storage (kPa) 86 ~ 106 Transportation (kPa) 70 ~ 106 Pollution Level IEC60721-3-3 Operation Class 3C3; Class 3S2 Storage Class 1C2; Class 1S2 Transportation Class 2C2; Class 2S2 If the AC motor drive is to be used under harsh environment with high level of contamination (e.g. dew, water, dust), make sure it is installed in an environment qualified for IP54 such as in a cabinet. Altitude Operation If the AC motor drive is installed at an altitude of 0~1,000m, follow normal operation restrictions. If it is installed at altitude 1,000 ~ 2,000 m, decrease 1% of rated current or lower 0.5 ºC of temperature for every 100m increase in altitude.

Maximum altitude for Corner Grounded TN system is 2,000m. For application over 2,000m, please contact Delta for more details. Package Drop Storage / Transportation ISTA procedure 1A (according to weight) IEC60068-2-31 Vibration 1.0 mm, peak to peak value range from 2 Hz to 13.2 Hz; 0.7 G ~ 1.0 G range from 13.2 Hz to 55 Hz; 1.0 G range from 55 Hz to 512 Hz. Comply with IEC 60068-2-6. Impact IEC / EN 60068-2-27 Operation Position Max. allowed offset angle ±10 º (under normal installation position) 10 10 Model Frame Top Cover Conduit Box Protection Level OperationTemperature VFDxxxxCP23x-21 VFDxxxxCP43x-21 VFDxxxxCP4Ex-21 VFDxxxxCP53x-21 VFDxxxxCP63x-xx Frame A ~ C 230 V: 0.75 ~ 30 kW 460 V:

0.75 ~ 37 kW 575 V: 1.5 ~ 15 kW 690 V: 18.5 ~ 37 kW Remove top cover Standard conduit plate IP20/UL Open Type 30 V & 460 V: -10 °C ~ 50 °C *1 575 V & 690 V: -10 °C ~ 50 °C Standard with top cover IP20/UL Type1/NEMA1 -10 °C ~ 40 °C Frame D ~ H 230 V: ≥ 37 kW 460 V: ≥ 45 kW 690 V: ≥ 45 kW N/A Conduit box IP20/UL Type1/NEMA1 -10 °C ~ 40 °C VFDxxxxCP23x-00 VFDxxxxCP43x-00 VFDxxxxCP63x-00 Frame D ~ H 230 V: ≥ 37 kW 460 V: ≥ 45 kW 690 V: ≥ 45 kW N/A No conduit box IP00 IP20 / UL Open Type Protection degree for the circled area is IP00; other areas are IP20 230 V & 460 V: -10 °C ~ 50 °C *1 690 V: -10 °C ~ 50 °C