Datasheet CP2000 690V * See dimensional drawing on Page 12~15. ** Connection for external DC-Choke. DELTA ELECTRONICS, INC.
6 of 21 Delta reserves the right to make ALL RIGHTS RESERVED changes without prior notice 690V 75 ~ 132kW Type number VFD-00 -21 750CP63A 900CP63A 1100CP63A 1320CP63A Rated power 690V (LD/ND) kW 575V (LD/ND) 75/55 55/45 90/75 75/55 110/90 90/75 132/110 110/90 Rated output current A RMS Rated output capacity kVA LD Overload % Rated input current A RMS 86 104 125 150 103 124 149 179 120% 60s (5min) 84 102 122 147 Rated output current A RMS Rated output capacity kVA ND Overload % Rated input current A RMS 67 86 104 125 80 103 124 149 120% 60s (5min) 160% 3s (25s) 66 84 102 122 Fundamental Power Factor >0.98 Efficiency % 97 Mains fuse (for UL:
Bussmann) JJS-175 JJS-200 JJS-250 JJS-300 Non-fuse current breaker A 175 200 225 300 Dimensions HxWxD mm -00: 589x370x300 -21: 715.8x370x300 Frame * -00: E1 -21: E2 Weight kg 61 1.5 Power cable entry mm -00: n.a. -21: 2x 92 4x 34 Signal cable entry mm -00: n.a. -21: 2x 22 Section of power cables (stranded) mm2 2*21.2 ~ 2*107 2*26.7 ~ 2*107 2*33.6 ~ 2*107 2*42.4 ~ 2*107 Cooling Fan Cooling air flow rate m3/hr 603.5 Carrier frequency (LD/ND) kHz 2~9 EMC-Filter External option DC-Choke Option ** DC-Bus connection Yes Brake chopper Built-in Recommended brake resistor /W 22/7200 18/9000 13.5/12000 11.3/14400 Minimum brake resistor value 12.2 8.2