Mitsubishi — 3.14.3.8 Communication

Chapter 3 Creating and Editing Screens  LOCKCOM / UNLOCKCOM (Lock COM Port / Unlock COM Port) Equation Lock COM Port Var1 = LOCKCOM (Var2, Var3) Unlock COM Port Var1 = UNLOCKCOM (Var2) Explanation LOCKCOM command locks COM port. Var1 is the response value after the communication, Var2 is the COM port and represents as constant 0(COM1), 1(COM2) or 2(COM3). Var3 is the communication time out time (unit is ms). When the specified communication time out time is reached, if the COM port cannot be locked, an error will be responsed. When Var3 is set to 0, it indicates that HMI will continuously wait without time limit. UNLOCKCOM command unlocks COM port.

Var2 is the COM port and represents as constant 0(COM1), 1(COM2) or 2(COM3). Remark  Var1: Response value after communication 1: Completed normally 0: Failed  Var1 can be internal memory only. Var2 and Var3 can be constant only.  When the communication commands are used in different macros, such as Screen Cycle Macro, Clock Macro, Background Macro, Befor/After Execute Macro, ON/OFF Macro, if LOCKCOM and UNLOCKCOM commands are not used, the different macros may have interferences and causes the error result. To ensure the correct communication and not to interrupt the communication at the same time, it is recommended to use these two commands. 3-362 Revision May, 2010