Mitsubishi — 3.4.1 Control Block

Chapter 3 Creating and Editing Screens Curve Control Register (CUCR)  Curve Sampling Flag Bits 0 to 3 (flags 1 to 4) control the curve (Trend Graph, X-Y Chart, X-Y distribution or Curve Input) sampling. When this flag is turned ON, HMI will read continuous data from the set PLC address to sample once, changes the data to the graph and shows it on HMI screen (For more details on the settings of curve element, please refer to section 3.8.10). To control the curve sampling flag again, this flag must be turned OFF and then ON again. Each curve element has to be assigned to a sampling flag where the sample flag is setup in the detail property of the element.

To enable the curve element, set the corresponding bit in this register. For example (refer to Table 3-4-1 and Fig. 3-4-5), if D2 or $17.0 is set to 1, the curves of figure 1 and 2 will be activated and show on the screen and the curves of figure 3 and 4 will not. When D2=1, it indicates that Bit 0 of D2 is 0 (0000 0000 0000 0001).

Revision May, 2010 3-29 Binary Display of Relative Bit Function Position (x) 0 0000 0000 0000 000x Curve Sampling Flag 1 1 0000 0000 0000 00x0 Curve Sampling Flag 2 2 0000 0000 0000 0x00 Curve Sampling Flag 3 3 0000 0000 0000 x000 Curve Sampling Flag 4 4-7 0000 0000 xxxx 0000 Reserved 8 0000 000x 0000 0000 Curve Clear Flag 1 9 0000 00x0 0000 0000 Curve Clear Flag 2 10 0000 0x00 0000 0000 Curve Clear Flag 3 11 0000 x000 0000 0000 Curve Clear Flag 4 12-15 xxxx 0000 0000 0000 Reserved