US Army Materiel Command AMCP 706-117 — Environmental Series, Part Three: Induced Environmental Factors

Downloaded from https://www.everyspec.com AMCP M0-117 -3-5.3 ELECTRICAL INSULATORS 4 HrL Silica sand and the majority of dusts (natural and industrial) usually deposited on insulator surfaces are poor .,onductors when dry. However, when wetted by high humidity, fog, or rain, the soluble compounds go CALW 01-I into solution forming a conducting elrctrolyte. The in- S ,LAWNP4TVgWILLS soluble particles remaining on the surface tend to retain 9 the electrolyte on the surface and to increase the effec- *- * *, эtive thickness of the moisture film. This can be a very DUS5WALL.

C06(al 2 =)-~I serious problem in areas such as California where the summers are rainless and dust can collect over a 3- to FIGURE 3.22. Rate of Ruat~n w Duijafall (At 4-mo period forming a thick layer of electrolyte when four~ lecdom, die figiw pion die race of rusdlng wetted by the first autumn rain (Ref. 36). of mild #aW ersusw diueall. and shows Miet cor6 As a result of the conductivity of such surface films, radon k Aow dma. se ,e~d in an Indwt&a awe the leakage currents flowing over contaminated power. 0@000)gdd so It Is In die ,xW wee (Llenwrwd W0liu0.) line insulators can beaon the order of one million times those that flow through clean, dry insulators. Fig. 3.23 (Ref.

36) compares the arcing distances for 60-Hz volt- humidity is below a critical level, which for many met. ages on clean and dry, clean and wet, and dirty and wet als is about 70 percent (Ref. 34); but they increase with insulators. In recent years, increase power require- increased humidity even in clean air, and they increase ments have caused power companies to gradually in- greatly with trame of sulfur dioxide in the air. In some crease transmission line voltages from about 250 kV to cases where suspended particulate levels correlated as high as 750 kV.

This has increased the rate of insula- well with weight lons due to corrosion, further analysis tar breakdown, resulting in flashover problems as well indicated that sulfur dioxide concentrations had the as the less dramatic power losse due to leakage cur- dominant influence on corrosion (Ref. 35). rents. TABLE 3-14.

CORROSION OF OPEN-HEARTH STEEL SPECIMENS Annual eai Location Type of atmosphere weight Reaie loss, g corrosivity Khartoum, Sudan ------------------- Dry inland ---------------- 0.16 1 Abisko, North Sweden--------------- Unpolluted ---------------- 0.46 3 Aro, Nigeria---------------------- Tropical inland------------ 1.19 8 Singapore, Malaya ----------------- Tropical marine------------ 1.36 9 Basrah, Iran---------------------- Dry inland ---------------- 1.39 9 Apape, Nigeria -------------------- Tropical narine------------ 2.29 15 State Col lege, Pa., USA ------------ Rural--------------------- 3.75 25 Berlin, Germany ------------------- Semi-industrial 4.71 32 Llenwrtyd Wells, British Isles------ Semnimarine---------------- 5.23 35 Celshot, British Islas ------------ Marine-------------------- 6.10 41 Sandy Hook, N.J., USA-------------- Marine-semil-industrial-..-- 7.34 50 Congella, South Africa------------- Marine-------------------- 7.34 50 Motherwell, British Isles ---------- Industrial ---------------- 8.17 55 Woolwich, British Isles ------------ Industrial ---------------- 8.91 60 Pittsburgh, Pa., USA--------------- Industrial ---------------- 9.65 65 Sheffield Univ., British Isles------ Industrial---------------- 11.53 78 Derby South End, British Isles------ Industrial---------------- 12.05 8`1 Derby North End, British Isles------ Industrial---------------- 12.52 84 Frodinghem, British Isles ---------- Industrial---------------- 14.81 100 3-27