Delta · 1 стр.
dru 24v10acz M EN 102019
Related manuals
Document text
(2) (3) Installation notes Technical data IMPORTANT SAFETY INSTRUCTIONS • Retain these instructions or go to www.deltapsu.com/manuals. This manual contains important safety instructions. • When replacing batteries, only use the same type of batteries listed under the “Recommended Batteries” section. • Proper disposal of batteries is required. Refer to the relevant local codes for disposal requirements. Delta DC-DC Power Supply DRU-24V10AC Figure 1 (1) (4) 1. Safety instructions • Switch explosion! • If the orange status LED is on, this indicates a failure in the installation. In this case, do not turn on power supply while the battery is connected. Danger of explosion!
• T and below the device as well as a lateral distance of 5mm to other units. • Please note that the enclosure of the device can become very hot depending on the ambient temperature and load of the unit. Risk of burns! • The terminals! • Do not introduce any objects into the unit! • Dangerous voltage present for at least 5 minutes after disconnecting all sources of power. • The unit is a built-in unit and must be installed in a cabinet or room (condensation free environment and indoor location) that is relatively free of conductive contaminants. • CAUTION: “FOR USE IN A CONTROLLED ENVIRONMENT” 2. Device description (Fig.
1) (1) Input/Output/Battery terminal block connector (2) Signal terminal block connector (3) LED display status (4) Universal mounting rail system 3. Mounting (Fig. 2) The unit can be mounted on 35mm DIN rails in accordance with EN60715. For Vertical Mounting, the device should be installed with Input/Output/Battery terminal block on the bottom. Each device is delivered ready to install. Snap on the DIN rail as shown in Fig. 2: 1. Pull the unit’s DIN rail latch DOWN. 2. Tilt the unit slightly upwards, hook the top end onto the DIN rail and push downwards until stopped. 3. Position the bottom front end against the DIN rail. 4. Push the unit’s latch DIN rail UP to lock. 4. Dismounting (Fig.
3) To uninstall, 1. Pull the unit’s DIN rail latch DOWN. 2. Tilt the bottom part of the unit out. 3. Push the unit up and pull out from the DIN rail. Typical Application Notes 6.1 Provide backup power during AC source interruption or failure 5. Connection The terminal block connectors allow easy and fast wiring. Power Supply + ‒ + ‒ ‒ + ‒ + I/P O/P BAT DC-UPS Battery 24V Load 1 Unbuffered Load Load 2 Buffered Load L N PE + ‒ ‒ + PE + ‒ PE Table 1 6.2 Can be combined with redundancy module (DRR-20 ) AC Input Refer to Fig. 1:
Stranded / Solid Torque (mmІ) (AWG) (Kgf-cm) (lb in) Power Supply 1 + ‒ Power Supply 2 + ‒ m o C 1 ni V 2 ni V + + ‒ (1) 2.1-3.3 14-12 6.3 5.4 (2) 0.21-3.3 24-12 6.3 5.4 L N PE L N PE Redundancy Module + OK Out + ‒ ‒ + ‒ + I/P O/P BAT DC-UPS Battery 24V + ‒ Load 1 Unbuffered Load ‒ + PE Load 2 Buffered Load ‒ + PE The wires between the DC-DC power supply and battery must not be longer than 2 x 2m (cord length 2m). For reliable and shock proof connections, the wire stripping length should be 7mm (see Fig. 4 (1)). Please ensure that wires are fully inserted into the connecting terminals as shown in Fig. 4 (2).
www.DeltaPSU.com Figure 6 AC Input Use appropriate copper cables designed to sustain operating temperature of: 1. 60°C, 60°C / 75°C for USA 2. At least 90°C for Canada. Delta Electronics (Thailand) Public Company Limited 909 Moo 4, E.P.Z., Bangpoo Industrial Estate, Tambon Prakasa, Amphur Muang Samutprakarn, Samutprakarn 10280, Thailand Tel: (662) 709-2800 Fax: (662) 709-2827 E-mail: info@deltapsu.com 110 Derating Curve (Discharge Current) 100 90 6. Signals Wiring Diagram (Fig. 5) Contact relay rating: 1A/30Vdc No polarity requirement Percentage of Max Load (%) 80 7. Typical Application Notes (Fig. 6) 1. Provide backup power during AC source interruption or failure. 2.
Can be combined with redundancy module (DRR-20 ). 60 70 40 50 20 30 (2) Make sure of the wiring is correct by following all local and national codes. (3) Do not modify or repair the unit. (4) Use caution to prevent any foreign objects from entering into the housing. (5) Do not use in wet locations. (6) Do not use the unit in area where moisture or condensation can be expected 10 0 -20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 Surrounding Air Temperature ( o C) Figure 7 . Input (DC) Nominal input voltage 24Vdc Voltage range 24-28Vdc Maximum input voltage Input Current Charging Mode: 0.5 ± 0.1A (25°C) Discharging Mode: 10A Max Charging time Charging Mode: > 80.0% Discharging Mode:
> 99.0% Output (DC) Nominal outp t voltage Discharging voltage Maximum output voltage 24Vdc typ. (depends on Vin) 22-28Vdc Output current Derating Component derating Short circuit / Overload 10A Max Refer to Fig. 7 Vin = 28.0Vdc, Max load Discharging Mode: Shutdown and no damage Recommended Batteries Battery types 24V, VRLA 2 x 12V, VRLA Battery capacity Battery fuse 3.3-12.0Ah Auto 15A / 58V, MINI (Littelfuse) or similar in the battery path. The battery fuse protects the wires between the battery and the DC-DC power supply.
General Data Type of housing Plastic (PC), enclosed LED signals Green LED On = Unit is fully charged Green LED Flashing = Unit is charging Orange LED Flashing = Unit is discharging Red LED On = Battery fail (no battery is connected) Orange LED On = Battery 24V or DC 24V reverse polarity Signal relay contacts DC OK = Contact is closed when battery is fully charged and the DISCHARGING = Contact is closed when the unit is discharging/ BATTERY FAIL = Contact is closed when the battery fails to function. MTBF > 500,000 hrs.
as per Telcordia SR-332 Dimensions (L x W x H) 91mm x 71mm x 55.6mm Weight 0.14kg Connection method Screw Connection Wire stripping length 7mm Operating temperature (surrounding air temperature) -20°C to +60°C (Refer to Fig. 7) Storage temperature -25°C to +85°C Humidity at +25°C, no condensation 5 to 95% RH Vibration - Operating IEC60068-2-6, Sine Wave: 10Hz to 500Hz @ 19.6m/s² (2G peak); 10 min per cycle, 60 min for all X, Y, Z directions - Non-Operating IEC60068-2-6, Random: 5Hz to 500Hz (2.09Grms); 20 min per axis for all X, Y, Z directions Shock (in all directions) - Operating IEC60068-2-27, Half Sine Wave:
4G for a duration of 22ms, 3 shocks for each 3 directions - Non-Operating IEC60068-2-27, Half Sine Wave: 50G for a duration of 11ms, 3 shocks for each 3 directions Pollution degree 2 Altitude (operating) 3000 Meters Safety and Protection Isolation voltage: Input & Output / PE Signal / PE Input & Output / Signal 1.0KVac 1.0KVac 1.0KVac Polarity protection Yes Protection degree IP20 Safety class Class III 1 Figure 2 stallation notes g this unit, read these operating and installation instructions carefully nd completely. 1 Figure 3 7 mm 1 2 Figure 4 2 3 4 3 2 Signals wiring diagram + ‒ DC 1 Isc DC OK 2 Voc DC-UPS 3 Isc Device Discharging 4 Voc 5 Isc BAT Fail 6 Voc Battery + ‒ Figure 5