2. Programming Concepts 3. DVP-ES2/EX2/SS2 series PLCs whose firmware version is 3.28 (or above), and DVP- SA2/SX2 series PLCs whose firmware version is 2.82 (or above) support this function. 4. Example: The value in C243 is fetched when there is a transition in X6’s signal from low to high. Program in the PLC: M1002 Enabling the fetching of the value in C243 M1000 FEND I601 M1000 Moving the value fetched from C243 to (D1,D0). IRET When the conditional contacts are closed, execute the ramp-down on the outputs Number M1334, M1335 Contents: 1. When M1334 or M1335 is enabled, execute API59 PLSR/DPLSR instructions on Y0 or Y2 to ramp-down when the conditional contacts are closed. 2.
When M1334 or M1335 is enabled, execute API158 DDRVI or API159 DDRVA instructions on CH0 (CH1) to ramp-down when the conditional contacts are closed. 3. This function is available for the followings: Function Group If the PLC detects that the external 24V voltage is unstable, the error LED flashes Number M1019 Contents: 1. When M1019 is ON, if the PLC detects the external 24V voltage is unstable, the error LED keeps flashing. 2. When M1019 is OFF, if the PLC detects the external 24V voltage is below 17.8V, the error LED flashes. After the PLC detects the external voltage is normal again for more than 2 seconds, the error LED stops flashing. 3. This function is available for the followings:
Function Group 2-71 EI SET M1598 DCNT C243 K100 DMOV D1150 D0 END ES2/ 12SA2/ Series ES2-C ES2-E SS2 26SE 28SA2 EX2 SX2 Firmware version or V3.42 V3.48 V1.0 V2.86 V3.28 V2.0 V3.0 later versions ES2/ 12SA2/ Series ES2-C ES2-E SS2 26SE 26SE 28SA2 EX2 SX2 Firmware version or V3.60 V3.60 V1.00 V3.00 V3.50 V1.92 V1.92 V3.0 later versions