Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 08 Operands: S : The number of times for the loop to be repeated. 09 Explanations: 1. FOR and NEXT instructions are used when loops are needed. No contact to drive the 2. “N” (number of times loop is repeated) may be within the range of K1 to K32767. If the range instruction is required. N ≦K1, N is regarded as K1. 3. An error will occur in the following conditions: • NEXT instruction is before FOR instruction. • FOR instruction exists but NEXT instruction does not exist.. • There is a NEXT instruction after the FEND or END instruction. • Number of FOR instructions differs from that of NEXT instructinos. 4.

FOR~NEXT loops can be nested for maximum five levels. Be careful that if there are too many loops, the increased PLC scan time may cause timeout of watchdog timer and error. Users can use WDT instruction to modify this problem. 3-56 Mnemonic Operands Function Controllers FOR Start of a FOR-NEXT Loop ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F FOR: 3 steps S * * * * * * * * * * * PULSE 16-bit 32-bit ES2/EX2 SS2 SA2 SE SX2 SA2 ES2/EX2 SS2 SA2 SE SX2 ES2/EX2 SS2 SX2 SE Mnemonic Function Controllers NEXT End of a FOR-NEXT Loop SA2 ES2/EX2 SS2 SX2 SE OP Descriptions Program Steps N/A No contact to drive the instruction is required.

NEXT: 1 step PULSE 16-bit 32-bit ES2/EX2 SS2 SA2 SE SX2 SA2 ES2/EX2 SS2 SA2 SE SX2 ES2/EX2 SS2 SX2 SE