3. Instruction Set API 37 Operands: S : Start No. of source device D : Start No. of destination device n 1 : Length of data to be shifted n 2 : Number of devices to be shifted as a group Explanations: 1. This instruction performs a left shift from source device of n 2 registers starting from S to 2. This instruction is generally used in pulse execution mode (WSFLP). destination device of n 1 registers starting from D . 3. The type of devices designated by S and D has to be the same, e.g. K n X, K n Y, K n M, and K n S as a category and T, C, and D as another category 4. Provided the devices designated by S and D belong to K n type, the number of digits of K n in S and D has to be the same.
5. Valid range of operand n1 , n2 : 1≤ n2 ≤ n1 ≤512 Program Example: 1. When X0 is triggered, WSFLP instruction shifts D10~D13 into data stack D20~D35 and D20~D35 also shift to the left with a group of 4 registers. 2. The figure below illustrates the left shift of the words in one scan D35~D32 → Carry D31~D28 → D35~D32 D27~D24 → D31~D28 D23~D20 → D27~D24 D13~D10 → D23~D20 completed X0 4 registers in one group shift to the left 5 Carry 1 3 4 2 3-99 Mnemonic Operands Function Controllers SA2 ES2/EX2 SS2 SX2 SE Controllers WSFL P Word Shift Left ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F WSFL, WSFLP:
9 steps S * * * * * * * D * * * * * * n 1 * * n 2 * * PULSE 16-bit 32-bit SA2 SX2 SS2 SA2 SX2 ES2/EX2 SS2 SA2 SE SX2 ES2/EX2 SS2 ES2/EX2 SE SE WSFLP D10 D20 K16 K4 D13 D12 D11 D10 D35 D34 D33 D32 D31 D30 D29 D28 D27 D26 D25 D24 D23 D22 D21 D20