3. Instruction Set A. Normally, PLC only refreshes pulse output when the pulse instruction is executed. You can use output pulse to check the pulse number but if the program is big, it may cause a bigger different result in such a long scan. B. When executing REF instruction with M1672-M1675, it can refresh the pulse output immediately. And when REF instruction works with M1672-M1675 flags, it is only used to refresh the pulse number not to refresh the actual inputs and outputs. C. Refer to program example 5 for reference. Program Example 1: When X0 = ON, PLC will refresh the status of input points X0 ~ X7 immediately without delay.
X0 When X0 = ON, the 4 output signals on Y0 ~ Y3 will be sent to output terminals immediately before Program Example 2: the program proceeds to END instruction. X0 K4 Program Example 3: When X0 = ON, I/O points starting from X10 or Y4 will all be refreshed. X0 X0 或 Program Example 4: For DVP-EX2/SX2 only: When X0 = ON and M1180 = ON, A/D signal in D1110~D1113 will be refreshed immediately regardless of the settings of operands D and n X0 3-119 REF X0 K8 REF Y0 REF X10 K8 REF Y4 K8 SET M1180 REF X0 K8 REF X0 K8 SET M1180