3. Instruction Set API 51 Operands: n : Response time (unit: ms) Explanation: 1. PLC provides digital input filters to avoid interference. The response time ( n) of X0 ~ X7 input filters can be adjusted by REFF instruction. The instruction sets the value specified in n to D1020 (X0 ~ X7 input filter time) directly. The instruction sets the value specified in n to D1021 (X10 ~ X17response time) for models including 28SS2 V3.42 /28SA2 V3.0 /26SE V2.0 and later versions. 2. When PLC turns from OFF to ON or the END instruction is reached, the response time is dictated by the value of D1020. 3. During program execution, the value in D1020 can be changed by using MOV instruction. 4.
When using REFF instruction during program execution, the modified response time will be move to D1020 and refreshed until next program scan.. 5. Range of n : = K2 ~ K20. Program Example: 1. When the power of PLC turns from OFF to ON, the response time of X0~X7 inputs is specified by the value in D1020. 2. When X20 = ON, REFF K5 instruction is executed, response time changes to 5 ms and takes affect the next scan. 3. When X20 = OFF, the REFF instruction will not be executed, the response time changes to 20ms and takes affect the next scan.
3-121 Mnemonic Operands Function Controllers SA2 REFF P Refresh and Filter Adjust ES2/EX2 SS2 SE SX2 Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F REFF, REFFP: 3 steps n * * PULSE 16-bit 32-bit SA2 SA2 ES2/EX2 SS2 SA2 SE SX2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 SE SE X20 REFF K5 X0 Y1 X20 REFF K20 X1 Y2 END REFF K5 END REFF K20