DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 68 Operands: S : Start device of the source data stack D : Start device of the destination data stack m : Transformation mode n : Length of source data stack Explanations: 1. For parameter settings of operand m , please refer to the following description. K, H, D devices can be specified by operand m. If the set value is not in the available range, no transformation or move operation will be executed and no error will be detected. 2. K, H, D devices can be specified by operand n, which indicates the length of the source data stack. The available range for n is 1~256.
If the set value falls out of available range, PLC will take the max value (256) or the min value (1) as the set value automatically. 3. The parameter settings and series to support the m operand are listed below: 3-178 Mnemonic Operands Function Controllers DTM P Data Transform and Move ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H Kn X KnY KnM KnS T C D E F DTM:
9 steps S * D * m * * * n * * * PULSE 16-bit 32-bit SA2 SA2 SA2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 SE SE SE Parameters Descriptions K0 Transform 8-bit data into 16-bit data (Hi-byte, Lo-byte) K1 Transform 8-bit data into 16-bit data (Hi-byte, Lo-byte) K2 Transform 16-bit data into 8-bit data (Hi-byte, Lo-byte) K3 Transform 16-bit data into 8-bit data (Hi-byte, Lo-byte) K4 Transform 8-bit HEX data into ASCII data (higher 4 bits, lower 4 bits) K5 Transform 8-bit HEX data into ASCII data (higher 4 bits, lower 4 bits) K6 Transform 8-bit ASCII data into HEX data (higher 4 bits, lower 4 bits) K7 Transform 8-bit ASCII data into HEX data (higher 4 bits, lower 4 bits) K8 Transform 8-bit GPS data into 32-bit floating point data K9 Calculate the optimal frequency function Available for ES2/EX2 V1.2, SS2/SA2/SX2/SE V1.0 K11 Conversion from local time to local sidereal time (longitude) Available for SA2 V1.0, SX2 V1.2, ES2/EX2 V2.0, SS2/SE V1.0