DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Operands: S : The Start of input devices D 1 : The Start of output devices D 2 : Device for storing switch input value n : Groups of switches ( n = 1~2) Explanations: 1. This instruction creates 1(2) group of 4-digit DIP switch by the combination of 4(8) consecutive input points starting from S and 4 consecutive output points starting from D 1 . The set value will be read in D 2 and the value in n specifies the number of groups (1~2) of the DIP switch. 2. n = K1, D 2 occupies 1 register. n = K2, D 2 occupies 2 consecutive registers. 3.
There is no limitation on the times of using this instruction in the program, however only one instruction is allowed to be executed at the same scan time. Program Example: 1. The first group of DIP switches consists of X20 ~ X23 and Y20 ~ Y23. The second group of switches consists of X24 ~ X27 and Y20 ~ Y23. When X10 = ON, the instruction will be executed and the set value of the first switch will be read and converted into BIN value then stored in D20. BIN value of 2 nd switch will be stored in D21. X0 2. When X0 = ON, Y20~Y23 are scanned repeatedly. M1029 = ON for a scan time when a scan cycle from Y20 to Y23 is completed.
X0 Y20 0.1s operation start 0.1s 0.1s Y21 0.1s Y22 0.1s interrupt 3-204 API Mnemonic Operands Function Controllers 72 DSW DIP Switch ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F DSW: 9 steps S * D 1 * D 2 * * * n * * PULSE 16-bit 32-bit ES2/EX2 SS2 SA2 SE SX2 SA2 SA2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 SE SE DSW X20 Y20 D20 K2 Y23 0.1s M1029 execution completed