3. Instruction Set Operands: S : English letters to be converted into ASCII code (A~Z or a~z only) D : Device for storing ASCII code Explanation: 1. The ASC instruction converts 8 English letters stored in S and save the converted ASCII code in D . The value in S can be input by WPLSoft or ISPSoft. 2. If PLC is connected to a 7-segment display while executing ASC instruction, the error message can be displayed by English letters 3. Flag: M1161 (8/16 bit mode switch) Program Example: When X0 = ON, A~H is converted to ASCII code and stored in D0~D3.
X0 D0 b15 b0 D1 D2 D3 48H (H) 47H (G) Low byte High byte When M1161 = ON, every ASCII code converted from b15 b0 D0 the letters will occupy the lower 8 bits (b7 ~ b0) of a D1 register and the upper 8 bits are invalid (filled by 0), D2 i.e. one register stores a letter D4 D3 D6 D5 D7 Low byte High byte 3-213 API Mnemonic Operands Function Controllers 76 ASC ASCII code conversion ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F ASC:
11 steps S D * * * PULSE 16-bit 32-bit ES2/EX2 SS2 SA2 SE SX2 SA2 ES2/EX2 SS2 SA2 SE SX2 ES2/EX2 SS2 SX2 SE ASC A B C D E F G H D0 42H (B) 41H (A) 44H (D) 43H (C) 46H (F) 45H (E) 00 H 41H (A) 00 H 42H (B) 00 H 43H (C) 00 H 44H (D) 00 H 45H (E) 00 H 46H (F) 00 H 47H (G) 00 H 48H (H)