Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set 2. Write the data to be sent into registers starting from D100 in advance. Write H12 (Forward running) into H2000 (VFD-B parameter address). M1002 Set up communication protocol as 9600,7,E,1 Retain communication protocol Set up communication time-out as 100ms 8-bit mode Pulse for sending request Write transmitting data in advance X0 Sending request M1123 Processing Received data Reset M1123. PLC  VFD-B, PLC sends: 01 06 2000 0012 02 07 VFD-B  PLC, PLC receives: 01 06 2000 0012 02 07 Registers for sent data (PLC sends out messages) Registers for received data (VFD-B responds with messages) 3.

The forward running function of Delta’s VFD series inverter can also be set by handy instruction API 102 FWD instruction through COM2/COM3 on PLC. 3-225 MOV H86 D1120 SET M1120 MOV K100 D1129 SET M1161 SET M1122 RS D100 K8 D120 K8 RST M1123 Register Data Explanation D100 low 01 H Address D101 low 06 H Function D102 low 20 H Data address D103 low 00 H D104 low 00 H Data content D105 low 12 H D106 low 02 H CRC CHK Low D107 low 07 H CRC CHK High Register Data Explanation D120 low 01 H Address D121 low 06 H Function D122 low 20 H Data address D123 low 00 H D124 low 00 H Data content D125 low 12 H D126 low 02 H CRC CHK Low D127 low 07 H CRC CHK High