DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 5. Communication protocol settings: D1036(COM1 RS-232) / D1120(COM2 RS-485) / D1109(COM3 RS-485) 3-236 COM1 COM2 COM3 Function Description - M1141 - MODRD/MODWR/MODRW parameter error (Exception Code exists in received data) Exception Code is stored in D1130 Errors - M1142 - Data receiving error of VFD-A handy instructions (FWD/REV/STOP/RDST/RSTEF) - D1130 - COM2 (RS-485) Error code returning from Modbus communication Content b0 Data Length 0: 7 data bits 1: 8 data bits Parity bit 00: None 01: Odd 11: Even b1 b2 b3 Stop bits 0: 1 bit 1: 2bits b4 Baud rate 0001(H1):110 bps 0010(H2): 150 bps 0011(H3): 300 bps 0100(H4):
600 bps 0101(H5): 1200 bps 0110(H6): 2400 bps 0111(H7): 4800 bps 1000(H8): 9600 bps 1001(H9): 19200 bps 1010(HA): 38400 bps 1011(HB): 57600 bps 1100(HC): 115200 bps 1101(HD): 500000 bps (COM2 / COM3) 1110 (HE): 31250 bps (COM2 / COM3) 1111 (HF): 921000 bps (COM2 / COM3) b5 b6 b7 b8 (D1120) STX 0: None 1: D1124 b9 (D1120) ETX1 0: None 1: D1125 b10 (D1120) ETX2 0: None 1: D1126 b11~b15 N/A