DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 9. Corresponding table between D1167~D1169 and the associated interrupt pointers. (Only lower 8 bits are valid) 10. Take standard MODBUS format for example: ASCII mode The communication protocol is in Modbus ASCII mode, i.e. every byte is composed of 2 ASCII characters. For example, 64Hex is ‘64’ in ASCII, composed by ‘6’ (36Hex) and ‘4’ (34Hex). Every character ‘0’…’9’, ‘A’…’F’ corresponds to an ASCII code. Start word (STX): ‘: ’ (3AH) Address: ‘0’ ‘0’:
Broadcasting to all drives (Broadcast) 3-238 Value Error Description H0005 Communication data length error COM Port I1□0 interrupt Special D COM1 I140 D1167 COM2 I150 D1168 COM3 I160 D1169 Field Name Descriptions STX Start word = ‘: ’ (3AH) Address Hi Communication address: The 8-bit address consists of 2 ASCII codes Address Lo Function Hi Function code: The 8-bit function code consists of 2 ASCII codes Function Lo DATA (n-1) Data content: n × 8-bit data content consists of 2n ASCll codes ……. DATA 0 LRC CHK Hi LRC check sum: 8-bit check sum consists of 2 ASCll code LRC CHK Lo END Hi End word:
END Hi = CR (0DH), END Lo = LF(0AH) END Lo Character ‘0’ ‘1’ ‘2’ ‘3’ ‘4’ ‘5’ ‘6’ ‘7’ ASCII code 30H 31H 32H 33H 34H 35H 36H 37H Character ‘8’ ‘9’ ‘A’ ‘B’ ‘C’ ‘D’ ‘E’ ‘F’ ASCII code 38H 39H 41H 42H 43H 44H 45H 46H