3. Instruction Set Operands: S : device to be rising-edge triggered Explanations: LDP should be connected to the left side bus line. When the associated device S is driven from OFF to ON, LDP will be ON for one scan cycle. Program Example: Ladder Diagram: Y1 Instruction Code: Operation: LDP X0 ; Load rising-edge contact X0 AND X1 ; Connect NO contact X1 in series OUT Y1 ; Drive Y1 coil Points to Note: 1. If the associated rising-edge contact is ON before PLC is power on, the contact will be activated after PLC is power on.
3-275 API Mnemonic Operands Function Controllers 90 LDP Rising–edge detection operation ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F LDP: 3 steps S * * * * * * PULSE 16-bit 32-bit SA2 SA2 SA2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 SE SE SE X0 X