3. Instruction Set Operands: S : Falling pulse output device Explanations: When X0 goes from ON to OFF (Falling-edge trigger), PLS instruction executes and S generates a cycle pulse for one operation cycle. Program Example: Ladder Diagram: X0 M0 Timing Diagram: X0 M0 A scan cycle Y0 Instruction Code: Operation: LD X0 ; Load NO contact X0 PLF M0 ; M0 falling-edge output LD M0 ; Load NO contact M0 SET Y0 ; Y0 latched (ON) 3-285 API Mnemonic Operands Function Controllers 99 PLF Falling-edge output ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F PLF:
3 steps S * * PULSE 16-bit 32-bit SA2 SA2 SA2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 SE SE SE PLF M0 SET Y0