DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Registers for received data (responding messages) 3-288 Register Data Descriptions D1070 low byte ‘0’ 30 H ADR 1 ADR 0 D1070 high byte ‘1’ 31 H D1071 low byte ‘0’ 30 H CMD 1 CMD 0 D1071 high byte ‘3’ 33 H D1072 low byte ‘0’ 30 H Number of data (count by byte) D1072 high byte ‘C’ 43 H D1073 low byte ‘0’ 30 H Content of address 2101 H 0100 H PLC automatically converts ASCII codes and store the converted value in D1050 D1073 high byte ‘1’ 31 H D1074 low byte ‘0’ 30 H D1074 high byte ‘0’ 30 H D1075 low byte ‘1’ 31 H Content of address 2102 H 1766 H PLC automatically converts ASCII codes and store the converted value in D1051 D1075 high byte ‘7’ 37 H D1076 low byte ‘6’ 36 H D1076 high byte ‘6’ 36 H D1077 low byte ‘0’ 30 H Content of address 2103 H 0000 H PLC automatically converts ASCII codes and store the converted value in D1052 D1077 high byte ‘0’ 30 H D1078 low byte ‘0’ 30 H D1078 high byte ‘0’ 30 H D1079 low byte ‘0’ 30 H Content of address 2104 H 0000 H PLC automatically converts ASCII codes and store the converted value in D1053 D1079 high byte ‘0’ 30 H D1080 low byte ‘0’ 30 H D1080 high byte ‘0’ 30 H D1081 low byte ‘0’ 30 H Content of address 2105 H 0136 H PLC automatically converts ASCII codes and store the converted value in D1054 D1081 high byte ‘1’ 31 H D1082 low byte ‘3’ 33 H D1082 high byte ‘6’ 36 H D1083 low byte ‘0’ 30 H Content of address 2106 H 0000 H PLC automatically converts ASCII codes and store the converted value in D1055 D1083 high byte ‘0’ 30 H D1084 low byte ‘0’ 30 H D1084 high byte ‘0’ 30 H D1085 low byte ‘3’ 33 H LRC CHK 1 LRC CHK 0 D1085 high byte ‘B’ 42 H