Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming API 107 Operands: S : Starting device for ASCII mode checksum n : Data length for LRC operation ( n = K1~K256) D : Starting device for storing the operation result Explanations: 1. n : n must be an even number. If n is out of range, an error will occur and the instruction will not be executed. At this time, M1067 and M1068 = ON and error code H’0E1A will be recorded in D1067. 2. 16-bit mode: When LRC instruction operates with M1161 = OFF, hexadecimal data starting from S is divided into high byte and low byte and the checksum operation is operated on n number of 3. 8-bit mode:

When LRC instruction operates with M1161 = ON, hexadecimal data starting from S bytes. After this, operation result will be stored in both hi-byte and low byte of D . is divided into high byte (invalid) and low byte and the checksum operation is operated on n number of low bytes. After this, operation result will be stored in low bytes of D (Consecutive 2 registers). 4. Flag: M1161 8/16-bit mode 3-308 Mnemonic Operands Function Controllers LRC P LRC checksum ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F LRC, LRCP: 7 steps S * n * * * D * 16-bit 32-bit SA2 SA2 SA2 SS2 SX2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 SE SE SE