Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set Operands: S : Source device D : Conversion result Explanation 1. The instruction converts the binary floating point value in S to decimal floating point value and stores the results in the register specified by D . 2. PLC floating point is operated by the binary floating point format. DEBCD instruction is the specific instruction used to convert binary floating point to decimal floating point. 3. Flag: M1020 Zero flag, M1021 Borrow flag, M1022 Carry flag If absolute value of the result exceeds the max. floating point value, carry flag M1022 = ON. If absolute value of the result is less than the min. floating point value, borrow flag M1021 = ON.

If the conversion result is 0, zero flag M1020 = ON. Program Example: When X0 = ON, the binary floating point value in D1, D0 will be converted to decimal floating point and the conversion result is stored in D3, D2. X0 Binary Floating Point 23 bits for real number, 8 bits for exponent 1 bit for sign bit [D2] * 10 [D3] Decimal Floating Point Exponent Real number Real number Exponent 3-325 API Mnemonic Operands Function Controllers 118 D EBCD P Float to scientific conversion ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F DEBCD, DEBCDP:

9 steps S * D * PULSE 16-bit 32-bit SA2 SA2 SA2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 SE SE SE DEBCD D0 D2 D1 D0 D3 D2