Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Example 3: To speed up the speed to reach the target temperature, we correct the sampling time as 4 seconds (D12 = K40, D30 = K4,000). The results are shown in the diagram below. From the diagram below, we see that the overall control time has been shortened as 37 minutes. Therefore, we find out that modifying the sampling time can speed up the time for reaching the target temperature. 3-358