Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set Registers for received data (responding messages) Analysis of the read status of PLC2 Y0~Y17: 1234H RTU Mode (M1143 = ON): When X0 = ON, MODRW instruction executes the function specified by Function Code 02 PLC2  PLC1 , PLC1receives: “ 01 02 02 34 12 2F 75 ” PLC1  PLC2 , PLC1sends:

“ 01 02 0500 0010 79 0A ” Registers for data to be sent (sending messages) Registers for received data (responding messages) 3-367 Register Data Descriptions D0 Low ‘0’ 30 H ADR 1 ADR 0 D0 High ‘1’ 31 H D1 Low ‘0’ 30 H CMD 1 CMD 0 D1 High ‘2’ 33 H D2 Low ‘0’ 30 H Number of Data (count by Byte) D2 High ‘2’ 32 H D3 Low ‘3’ 33 H Content of address 0500H~ 0515H 1234 H PLC automatically converts ASCII codes and store the converted value in D1296 D3 High ‘4’ 34 H D4 Low ‘1’ 31H D4 High ‘2’ 32H D5 Low ‘B’ 52H LRC CHK 1 D5 High ‘5’ 35 H LRC CHK 0 Device Status Device Status Device Status Device Status Y0 OFF Y1 OFF Y2 ON Y3 OFF Y4 ON Y5 ON Y6 OFF Y7 OFF Y10 OFF Y11 ON Y12 OFF Y13 OFF Y14 ON Y15 OFF Y16 OFF Y17 OFF Register Data Descriptions D1256 Low 01 H Address D1257 Low 02 H Function D1258 Low 05 H Y0 = H0500 Starting Data Address D1259 Low 00 H D1260 Low 00 H Number of Data (count by word) D1261 Low 10 H D1262 Low 79 H CRC CHK Low D1263 Low 0A H CRC CHK High Register Data Descriptions D0 Low 01 H Address D1 Low 02 H Function D2 Low 02 H Number of Data (Byte) D3 Low 34 H Content of address H0500~H0515 D4 Low 12 H D5 Low 2F H CRC CHK Low D6 Low 75 H CRC CHK High