DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Registers for received data (responding messages) RTU mode (M1143 = ON) When X0 = ON, MODRW instruction executes the function specified by Function Code 06 PLC VFD-B, PLC sends: “01 06 2000 1770 8C 1E” VFD-B PLC, PLC receives: “ 01 06 2000 1770 8C 1E ” Registers for data to be sent (sending messages) Registers for received data (responding messages) 3-380 Register Data Descriptions D1259 High byte ‘0’ 30 H D1260 Low byte ‘1’ 31 H Data content H1770 = K6000. The content of register D50 D1260 High byte ‘7’ 37 H D1261 Low byte ‘7’ 37 H D1261 High byte ‘0’ 30 H D1262 Low byte ‘5’ 35 H LRC CHK 1 LRC CHK 0 Checksum:
LRC CHK (0,1) D1262 High byte ‘2’ 32 H Register Data Descriptions D1070 Low byte ‘0’ 30 H ADR 1 ADR 0 D1070 High byte ‘1’ 31 H D1071 Low byte ‘0’ 30 H CMD 1 CMD 0 D1071 High byte ‘6’ 36 H D1072 Low byte ‘2’ 32 H Data Address D1072 High byte ‘0’ 30 H D1073 Low byte ‘0’ 30 H D1073 High byte ‘0’ 30 H D1074 Low byte ‘1’ 31 H Data content D1074 High byte ‘7’ 37 H D1075 Low byte ‘7’ 37 H D1075 High byte ‘0’ 30 H D1076 Low byte ‘6’ 36 H LRC CHK 1 LRC CHK 0 D1076 High byte ‘5’ 35 H Register Data Descriptions D1256 Low byte 01 H Address D1257 Low byte 06 H Function D1258 Low byte 20 H Data Address D1259 Low byte 00 H D1260 Low byte 17 H Data content H1770 = K6000.
The content of register D50 D1261 Low byte 70 H D1262 Low byte 8C H CRC CHK Low D1263 Low byte 1E H CRC CHK High Register Data Descriptions D1070 Low byte 01 H Address D1071 Low byte 06 H Function D1072 Low byte 20 H Data Address D1073 Low byte 00 H D1074 Low byte 17 H Data content D1075 Low byte 70 H