Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set ASCII mode (M1143 = OFF) When X0 = ON, MODRW instruction executes the function specified by Function Code H0F. PLC1  PLC2, PLC sends: “ 01 0F 0500 0010 02 3412 93 ” Registers for data to be sent (sending messages) PLC2  PLC1, PLC receives: “ 01 0F 0500 0010 DB ” Registers for received data (responding messages) 3-383 Register Data Descriptions D1256 Low byte ‘0’ 30 H ADR 1 ADR 0 Device address: ADR (1,0) D1256 High byte ‘1’ 31 H D1257 Low byte ‘0’ 30 H CMD 1 CMD 0 Control parameter:

CMD (1,0) D1257 High byte ‘F’ 46 H D1258 Low byte ‘0’ 30 H Data Address D1258 High byte ‘5’ 35 H D1259 Low byte ‘0’ 30 H D1259 High byte ‘0’ 30 H D1260 Low byte ‘0’ 30 H Number of Data (count by bit) D1260 High byte ‘0’ 30 H D1261 Low byte ‘1’ 31H D1261 High byte ‘0’ 30 H D1262 Low byte ‘0’ 30 H Byte Count D1262 High byte ‘2’ 32 H D1263 Low byte ‘3’ 33 H Data contents 1234H Content of register D0 D1263 High byte ‘4’ 46 H D1264 Low byte ‘1’ 33 H D1264 High byte ‘2’ 46 H D1265 Low byte ‘9’ 39 H LRC CHK 1 Checksum:

LRC CHK (0,1) D1265 High byte ‘3’ 33 H LRC CHK 0 Register Data Descriptions D1070 Low byte ‘0’ 30 H ADR 1 ADR 0 D1070 High byte ‘1’ 31 H D1071 Low byte ‘0’ 31 H CMD 1 CMD 0 D1071 High byte ‘F’ 46 H D1072 Low byte ‘0’ 30 H Data Address D1072 High byte ‘5’ 35 H D1073 Low byte ‘0’ 30 H D1073 High byte ‘0’ 30 H D1074 Low byte ‘0’ 30 H Number of Data(count by bit) D1074 High byte ‘0’ 30 H D1075 Low byte ‘1’ 31 H D1075 High byte ‘0’ 30 H D1076 Low byte ‘D’ 44 H LRC CHK 1 LRC CHK 0 D1076 High byte ‘B’ 42 H