DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 2. Registers for setting ramp up/down time and start/end frequency: Output Y0: Sample time of ramp-up Pulse output frequency Ramp-up slope Start freq. End freq. Y0(D1340) Y0 (D1340) Min: 6Hz Min: 6Hz Numbers of output pulses Ramp down time Ramp up time Default: 100ms Current position Default: 100ms Y0(D1343) Y0(D1343) This instruction can be used many times in user program, but only one instruction will be activated at a time. For example, if Y0 is currently activated, other instructions use Y0 won’t be executed. Therefore, instructions first activated will be first executed.
After activating the instruction, all parameters cannot be modified unless instruction is OFF. 3. Associated Flags: 3-408 M1029: CH0 (Y0, Y1) pulse output execution completed. M1102: CH1 (Y2, Y3) pulse output execution completed M1078: CH0 (Y0, Y1) pulse output pause (immediate) M1104: CH1 (Y2, Y3) pulse output pause (immediate) M1108: CH0 (Y0, Y1) pulse output pause (ramp down). M1110: CH1 (Y2, Y3) pulse output pause (ramp down) M1119: Enabling the DDRVI/DDRVA two speed output function M1156: Enabling the mask and alignment mark function on I400/I401(X4) corresponding to Y0. M1158: Enabling the mask and alignment mark function on I600/I601(X6) corresponding to Y2. M1305:
Reverse Y1 pulse output direction in high speed pulse output instructions M1306: Reverse Y3 pulse output direction in high speed pulse output instructions M1347: Auto-reset Y0 when high speed pulse output completed M1524: Auto-reset Y2 when high speed pulse output completed M1534: Enable ramp-down time setting on Y0. Has to be used with D1348 M1535: Enable ramp-down time setting on Y2. Has to be used with D1349.