3. Instruction Set Points to note: 1. There are two methods to correct built-in RTC: Correcting by API167 TWR instruction Setting by peripheral device Please refer to explanation of instruction TWR (API 167) Using WPLSoft / ISPSoft (Ladder editor) 2. Display 4-digit year data: D1319 only stores the 2-digit year in A.D. If 4-digit year data is required, please insert the following instruction at the start of program. M1002 Display 4-digit year data The original 2-digit year will be switched to a 4-digit year, i.e. the 2-digit year will pluses 2,000.
If users need to write in new time in 4-digit year display mode, only a 2-digit year data is applicable (0 ~ 99, indicating year 2000 ~ 2099). For example, 00 = year 2000, 50 = year 2050 and 99 = year 2099. However, 2000 ~ 2099 can be written in ES2/EX2 V3.0, SS2 V3.2, SA2 V2.6, SX2 V2.4, and SE V1.6 (and above). Flags and special registers for RTC 3-419 SET M1016 Device Content Function M1016 Year display mode of RTC OFF: D1319 stores 2-digit year data in A.D. ON: D1319 stores 2-digit year data in A.D + 2000 M1017 ±30 seconds correction on RTC Correction takes place when M1017 goes from OFF to ON (Second data in 0 ~ 29: reset to 0. Second data in 30 ~ 59:
minute data pluses 1, second data resets) Device Content Range D1313 Second 0-59 D1314 Minute 0-59 D1315 Hour 0-23 D1316 Day 1-31 D1317 Month 1-12 D1318 Day (Mon. ~ Sun.) 1-7 D1319 Year 0-99 (two digit year data)