DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Operands: S : Source device D : Operation result (BIN value) Explanations: 1. GBIN instruction converts the Gray Code in S to BIN value and stores the converted result in specified register D . 2. This instruction can be used to read the value from an absolute position type encoder (generally a Gray Code encoder) which is connected to the PLC inputs. The Gray code is converted to BIN value and stored in the specified register. 3. Available range of S : 16-bit instruction : 0~32,767 32-bit instruction : 0~2,147,483,647 4. If operand S exceeds the available range, operation error occurs and the instruction is 5.
If operands S and D use device F, only 16-bit instruction is applicable. disabled. Program Example: When X20 = ON, the Gray Code value in the absolute position type encoder connected to X0~X17 inputs is converted to BIN value and stored in D10. X20 D10 X17 X0 K4X0 GRAY CODE 6513 H1971=K6513 b15 b0 3-426 API Mnemonic Operands Function Controllers 171 D GBIN P Gray Code BIN ES2/EX2 SS2 SA2 SX2 SE Typ e OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F GBIN, GBINP: 5 steps DGBIN, DGBINP:
9 steps S * * * * * * * * * * * D * * * * * * * * PULSE 16-bit 32-bit SS2 SA2 SA2 SA2 ES2/EX2 SX2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 SE SE SE GBIN K4X0 0 0 0 1 0 1 0 1 1 1 0 0 1 0 0 1 0 0 0 1 1 0 0 1 0 1 1 1 0 0 0 1