Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Operands: S 1 : Floating point n dividend S 2 : Floating point divisor D: Quotient Explanations: 1. DIVR instruction divides S 1 by S 2 and stores the operation result in D 2. In DIVR instruction, floating point values can be directly entered into S 1 and S 2 . 3. In DDIVR instruction, floating point values (e.g. F1.2) can be either entered directly into S 1 and S 2 or stored in data registers for operation. 4. When S 1 and S 2 is specified as data registers, the function of DDIVR instruction is the same as API 123 EDIV instruction. 5. If S 2 = 0, operation error occurs and M1067 = ON, M1068 = ON.

D1067 stores the error code 0E19 (HEX). 6. Flags: M1020 (Zero flag), M1021 (Borrow flag) and M1022 (Carry flag) If absolute value of the result exceeds max floating point value, carry flag M1022 = ON. If absolute value of the result is less than min. floating point value, borrow flag M1021 = ON. If the conversion result is 0, zero flag M1020 = ON. Program example 1: When X0 = ON, divide floating point number F1.200E+0 (Input F1.2, and scientific notation F1.200E+0 will be displayed on ladder diagram. Users can set monitoring data format as float on the function View) with F2.200E+0 and store the obtained result F0.545E+0 in D10 and D11. X0 Program example 2:

When X1= ON, divide the floating point number value (D1, D0) by (D11, D10) and store the obtained quotient into registers (D21, D20). X1 3-430 API Mnemonic Operands Function Controllers 175 D DIVR P Floating point division ES2/EX2 SS2 SA2 SX2 SE Typ e OP Bit Devices X Y M S Word devices Program Steps Y M S K H KnX KnY KnM KnS T C D E F DDIVR: 13 steps S 1 * S 2 * D * PULSE 16-bit 32-bit SA2 SA2 SA2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 ES2/EX2 SS2 SX2 SE SE SE DDIVR F1.200E+0 F2.200E+0 D10 1 DDIVR D0 D10 D20