Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set API 215~ 217 Operands: S 1 : Source device 1 S 2 : Source device 2 Explanations: 1. This instruction conducts logic operation between the content in S 1 and S 2 . If the result is not “0”, the continuity of the instruction is enabled. If the result is “0”, the continuity of the instruction is disabled. 2. LD# ( #: &, |, ^) instruction is used for direct connection with Left bus bar. 3. Operation: & : Logic “AND” operation, | : Logic “OR” operation, ^ : Logic “XOR” operation 4. When 32-bit counters (C200 ~ C254) are used in this instruction, make sure to adopt 32-bit instruction (DLD#).

If 16-bit instruction (LD#) is adopted, a “program error” will occur and the ERROR indicator on the MPU panel will flash. Program Example: 1. When the result of logical AND operation between C0 and C10 ≠ 0, Y20 = ON. 2. When the result of logical OR operation between D200 and D300 ≠ 0 and X1 = ON, Y21 = ON and latched. Y20 SET X1 Y21 3-499 Mnemonic Operands Function Controllers D LD# Contact Type Logic Operation ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F LD#: 5 steps DLD#:

9 steps S 1 * * * * * * * * * * * S 2 * * * * * * * * * * * PULSE 16-bit 32-bit ES2/ EX2 SS2 SA2/ SE SX2 ES2/ SA2/ ES2/ SA2/ SS2 SX2 SS2 SX2 EX2 SE EX2 SE 16 -bit 32 -bit Continuity Discontinuity API No. instruction instruction condition condition 215 LD& DLD& S 1 & S 2≠0 S 1 & S 2=0 216 LD| DLD| S 1 | S 2≠0 S 1 | S 2=0 217 LD^ DLD^ S 1 ^ S 2≠0 S 1 ^ S 2=0 LD & C0 C10 LD | D200 D300