Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set 273 Operands: S: Reference source device n: Reference bit Explanations: 1. For ES2/EX2 models, only V1.20 or above supports the function. 2. Available range for the value in operand n : K0~K15 for 16-bit instruction; K0~K31 for 32-bit instruction. 3. BOR instruction is used to connect NO contact in parallel, whose state is defined by the reference bit n in reference device D , i.e. if the bit specified by n is ON, the NO contact will be ON, and vice versa. Program Example: X0 Y1 Instruction: Operation:

LD X0 Load NO contact X0 BOR D0 K0 Connect NO contact in parallel, whose state is defined by bit0 of D0 OUT Y1 Drive coil Y1 3-513 Mnemonic Operands Function Controllers D BOR Connect NO Contact in Parallel by Specified Bit ES2/EX2 SS2 SA2 SX2 SE Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F BOR: 5 steps DBOR: 9 steps S * * * * * * n * * * * * * * * * * * PULSE 16-bit 32-bit ES2/ EX2 SS2 SA2/ SE SX2 ES2/ SA2/ ES2/ SA2/ SS2 SX2 SS2 SX2 EX2 SE EX2 SE BOR D0 K0