3. Instruction Set 336 Operands Node : Station address which is reset Para : Setting value of the parameter Ok : The reset completion flag Err : The reset error flag Explanation 1. RSTD instruction is supported for firmware V3.60 or later. And it can work with CANopen DS301 mode and Delta special mode. 2. Before the RSTD instruction is used in Delta special instruction mode, make sure that all Delta drives have been initialized via the INITC instruction and they once worked normally. 3. When used in CANopen DS301 mode, the RSTD instruction works as the NMT communication function and can switch network states via the Para parameter. 4.
When CAN communication port is specified to work in Delta special driver mode, the value of Node can be 0 (for the broadcast function) and 1~8 which are for servo station addresses only. When the station address exceeds the range, the PLC will not perform the reset action and the Err flag turns on. (Refer to the explanation of D6001 for error codes) 5. When CAN communication port is specified to work in CANopen DS301 mode, the value of Node is in the range of 0~16 and 0 (for the broadcast function). When the value exceeds the range, the PLC will not perform the NMT communication and the Err flag turns on. (Refer to the explanation of D6001 for error codes) 6.
The setting value of Para is only applicable to CANopen DS301 mode. The settings for Para (NMT service code) are listed in the following table. If the setting value is not one of the values in the table, the Err flag turns on. 3-565 Mnemonic Operands Function Controllers ES2-C RSTD Node,Para, Ok,Err Sending Reset or NMT command Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F RSTD: 9 steps Node * * * Para * Ok * Err * PULSE 16-bit 32-bit ES2-C