Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set API 342 Operands S 1 : Station address of servo S 2 : Request code S 3 : Index S 4 : Sub-index S 5 : Read/write device D : Device D 1 : Communication completion flag Explanation 1. It is not available for pulse type instructions. Do not use pulse type contact. 2. For firmware V3.48 or later, it can work with Delta special mode. The range of S 1 is 1–8. If the setting value is exceeding this range, an error occurs and M1067 will be set to ON, D1067 = 0x0E1A. 3. For firmware V3.60 or later, it can work with Delta special mode and CANopen DS301 mode. This instruction reads and writes CANopen communication data to the servo at the address specified in S 1 .

The range of S 1 is 1–127. If the value is out of range ( 127), the minimum or maximum value is automatically processed by the instruction as the value of S 1 . 3-591 Mnemonic Operands Function Controllers ES2-C COPRW S 1, S 2, S 3, S 4, S 5, D 1 Read and write CANopen communication data Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F COPRW: 13 steps S 1 * * S 2 * * * S 3 * * * S 4 * * * S 5 * D 1 * PULSE 16-bit 32-bit ES2-C