Delta DVP-ES2 — 3.8 Detailed Instruction Explanation

3. Instruction Set 10. Most of the parameters in Delta ASDA are displayed in the decimal format. You can convert the address. parameters into index addresses, see the example below. 0 is a fixed value for the sub index Example: The index address of PX-YY=0x2000 + ( X ) + YY P2-10 = 0x2000 + ( 0x0002 ) + 0x000A = 0x220A P5-04 = 0x2000 + ( 0x0005 ) + 0x0004 = 0x2504 P1-44 = 0x2000 + ( 0x0001 ) + 0x002C = 0x212C 11. Most of the parameters in Delta inverter are also displayed in the decimal format. Use the following formula to convert the parameters. Example:

The index address of PXX-YY=0x2000 + XX (hexadecimal); The sub index address is YY+1 (hexadecimal) The index address of P10-15 = 0x2000 + 0x000A = 0x200A The sub index address is 0x0F+1= 0x10 Example 1. When M0 changes from OFF to ON, the INITC instruction starts to initialize the servos at station addresses 1–3, until M1615 is ON. 2. When M20 changes from OFF to ON, the PLC writes the 2-byte data in D100-D104, and reads the value of P4-07 and stores the value in D105, using the COPRW instruction. When the writing is complete, M100-M104 is ON. 3-593