Delta DVP-ES2 — 4.4 PLC Device Address

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming An example of exception response of command code 01H and exception 02H: Sent message: Feedback message:

4.4 PLC Device Address 4-10 Field Name Example (Hex) START No data input ≥ 10 ms Slave Address 01 Command code 01 Starting Address 04 00 Number of Points 00 10 CRC CHK Low 3C CRC CHK High F6 END No data input ≥ 10 ms Field Name Example (Hex) START No data input ≥ 10 ms Slave Address 01 Function 81 Exception Code 02 CRC CHK Low C1 CRC CHK High 91 END No data input ≥ 10 ms Effective Range MODBUS Device Range SA2/SE Address ES2/EX2 SS2 Address SX2 S 000~255 000~1023 000~1023 000001~000256 0000~00FF S 256~511 000257~000512 0100~01FF S 512~767 000513~000768 0200~02FF S 768~1023 000769~001024 0300~03FF X 000~377 (Octal) 000~377 000~377 101025~101280 0400~04FF Y 000~377 (Octal) 000~377 000~377 001281~001536 0500~05FF T 000~255 bit 000~255 000~255 001537~001792 0600~06FF 000~255 word 000~255 000~255 401537~401792 0600~06FF M 000~255 0000 ~ 4095 0000~4095 002049~003584 0800~08FF M 256~511 0900~09FF M 512~767 0A00~0AFF M 768~1023 0B00~0BFF M 1024~1279 0C00~0CFF M 1280~1535 0D00~0DFF