Delta DVP-ES2 — 5.5 Types of Sequences

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 5.5 Types of Sequences Single Sequence: The basic type of sequence The first step in a step ladder diagram is called initial step, ranged as S0 ~ S9. The steps following the initial step are general steps numbered as S10 ~ S1023. When IST instruction is applied, S10 ~ S19 will become the steps for zero return operation. 1. Single Sequence without Divergence and Convergence After a sequence is completed, the control power on the steps will be transferred to the initial step. Step Ladder Diagram SFC diagram M1002 S0 X0 S20 Y0 X1 S30 Y1 X2 S40 Y2 X3 S50 Y3 X4 S60 Y4 X5 S0 5-12 Device Description D1045 No.

of the 6th step point which is ON D1046 No. of the 7th step point which is ON. D1047 No. of the 8th step point which is ON M1002 ZRST S0 SET S0 S0 X0 S SET S20 S20 S Y0 X1 SET S30 S30 S Y1 X2 SET S40 S40 S Y2 X3 SET S50 S50 S Y3 X4 SET S60 S60 S Y4 X5 S0 RET END 02 ZRST S0 S127 SET S0 END SET S20 SET S30 SET S40 SET S50 SET S60